510E71TT6 — Three-phase 400 V → 400 V
Galvanic isolation and circuit separation
Technical specifications
Input voltage
400 V
400 V
Output voltage
400 V
400 V
Power
100 kVA
100 kVA
Frequency
50/60 Hz
50/60 Hz
Thermal class
<31,5 kVA: F (140ºC) / Ta=40ºC - ≥31,5 kVA: H (165ºC) / Ta=40ºC
<31,5 kVA: F (140ºC) / Ta=40ºC - ≥31,5 kVA: H (165ºC) / Ta=40ºC
Degree of protection
IP-65
IP-65
Cooling
AN
AN
Protection against electric shock
Class I
Class I
Test voltage
4,5 KV
4,5 KV
Vector group
Dyn11
Dyn11
Standards
IEC-UNE-EN 61558, CE UL 5085-1 / UL 5085-2
IEC-UNE-EN 61558, CE UL 5085-1 / UL 5085-2
Dimensions and weight
| A | 1380 |
|---|---|
| B | 980 |
| C | 1444 |
| d | 600 |
| e | 890 |
| Enclosure | 65 |
| Weight | 713 |
| EAN | 8435012210154 |
Dimension reference
Dimensions A, B, C, d and e in the table correspond to those shown in this image.

Application
Galvanic isolation and circuit separation
Three-phase 400 V → 400 V. This family is designed for galvanic isolation and circuit separation in a three-phase configuration.
Electrical configuration: input 400 V, output 400 V, range 1 a 400 kVA. Final selection should consider actual installation and protection conditions.
