HomeProduct families › RI0

RI0 — Reactors for harmonic filtering on single-phase lines

Reactors for harmonic filtering on single-phase lines. This family is designed for harmonic filtering and protection on ac lines in a single-phase configuration.

Electrical configuration: input 230 V, output Según referencia, range 2 a 70 A. Final selection should consider actual installation and protection conditions.

Technical data

Line input voltage
230 V
L (mH)
Según referencia
Frequency
50/60 Hz
Thermal class
F (140ºC) / Ta=40ºC
Degree of protection
IP-00
Cooling
AN
Protection against electric shock
Class I
Test voltage
4,5 KV
Vector group
I
Relevant parameters
Uk = 3.35%

Application

Harmonic filtering and protection on AC lines

Reactors for harmonic filtering on single-phase lines. This family is designed for harmonic filtering and protection on ac lines in a single-phase configuration.

Electrical configuration: input 230 V, output Según referencia, range 2 a 70 A. Final selection should consider actual installation and protection conditions.

References and dimensions

ReferenceCurrentLine input voltageL (mH)A × B × CWeight
002230RI02 A230 V9.8 mH66 × 69 × 78 mm0.7 kg
005230RI05 A230 V4.9 mH66 × 69 × 78 mm0.7 kg
010230RI010 A230 V2.45 mH75 × 74 × 77 mm1.2 kg
015230RI015 A230 V1.63 mH84 × 83 × 80 mm1.25 kg
020230RI020 A230 V1.22 mH96 × 96 × 91 mm2.5 kg
035230RI035 A230 V0.7 mH108 × 107 × 114 mm4.5 kg
050230RI050 A230 V0.49 mH126 × 123 × 121 mm6.5 kg
070230RI070 A230 V0.35 mH126 × 130 × 164 mm7 kg

Dimension reference

Dimensions A, B, C, d and e in the table correspond to those shown in this image.

Dimension reference · RI0

Request a quote