HomeProduct families › E75TT6

E75TT6 — Three-phase step-up 230 V → 400 V

Three-phase step-up transformer intended for homes and residential installations with a 230 V three-phase supply that need to power equipment designed for 400 V. Unlike an autotransformer, it maintains galvanic separation between the incoming supply and the output.

The IP65 version provides a higher level of protection against dust and water, making it more suitable where the residential installation requires a more protected enclosure. Final location must comply with the intended installation and service conditions. It is suitable where electrical separation from the original supply is required in addition to voltage conversion. It is also designed for residential use with quiet operation and low energisation inrush current, reducing the risk of nuisance circuit-breaker tripping.

Technical data

Input voltage
230 V
Output voltage
400 V
Frequency
50/60 Hz
Thermal class
<25 kVA: F (140ºC) / Ta=40ºC - ≥25 kVA: H (165ºC) / Ta=40ºC
Degree of protection
IP-65
Cooling
AN
Protection against electric shock
Class I
Test voltage
4,5 KV
Vector group
Dyn11
Relevant parameters
Not applicable

Application

230 V to 400 V step-up with isolation for residential use

Three-phase step-up transformer intended for homes and residential installations with a 230 V three-phase supply that need to power equipment designed for 400 V. Unlike an autotransformer, it maintains galvanic separation between the incoming supply and the output.

The IP65 version provides a higher level of protection against dust and water, making it more suitable where the residential installation requires a more protected enclosure. Final location must comply with the intended installation and service conditions. It is suitable where electrical separation from the original supply is required in addition to voltage conversion. It is also designed for residential use with quiet operation and low energisation inrush current, reducing the risk of nuisance circuit-breaker tripping.

References and dimensions

ReferencePowerInput voltageOutput voltageA × B × CWeight
325E75TT62.5 kVA230 V400 V500 × 372 × 584 mm51 kg
340E75TT64 kVA230 V400 V500 × 372 × 584 mm65 kg
363E75TT66.3 kVA230 V400 V660 × 490 × 734 mm102 kg
380E75TT68 kVA230 V400 V660 × 490 × 734 mm110 kg
410E75TT610 kVA230 V400 V660 × 490 × 734 mm133 kg
413E75TT613 kVA230 V400 V660 × 490 × 734 mm150 kg
416E75TT616 kVA230 V400 V660 × 490 × 734 mm180 kg
420E75TT620 kVA230 V400 V660 × 490 × 734 mm202 kg
425E75TT625 kVA230 V400 V980 × 800 × 1034 mm293 kg
431E75TT631.5 kVA230 V400 V980 × 800 × 1034 mm317 kg
440E75TT640 kVA230 V400 V980 × 800 × 1034 mm378 kg
450E75TT650 kVA230 V400 V1380 × 980 × 1444 mm558 kg

Dimension reference

Dimensions A, B, C, d and e in the table correspond to those shown in this image.

Dimension reference · E75TT6

Request a quote