B72TU2 — Single-phase 230 V → 230 V for IT networks
Single-phase 230 V → 230 V for IT networks. This family is designed for galvanic isolation and circuit separation in a single-phase configuration.
Electrical configuration: input 230 V, output 230 V, range 10 a 50 kVA. Final selection should consider actual installation and protection conditions.
Technical data
Input voltage
230 V
230 V
Output voltage
230 V
230 V
Frequency
50/60 Hz
50/60 Hz
Thermal class
F (140ºC) / Ta=40ºC
F (140ºC) / Ta=40ºC
Degree of protection
IP-23
IP-23
Cooling
AN
AN
Protection against electric shock
Class II
Class II
Test voltage
4,5 KV
4,5 KV
Vector group
Ii0
Ii0
Relevant parameters
Not applicable
Not applicable
Application
Galvanic isolation and circuit separation
Single-phase 230 V → 230 V for IT networks. This family is designed for galvanic isolation and circuit separation in a single-phase configuration.
Electrical configuration: input 230 V, output 230 V, range 10 a 50 kVA. Final selection should consider actual installation and protection conditions.
References and dimensions
| Reference | Power | Input voltage | Output voltage | A × B × C | Weight |
|---|---|---|---|---|---|
| 410B72TU2 | 10 kVA | 230 V | 230 V | 575 × 460 × 606 mm | 82 kg |
| 413B72TU2 | 13 kVA | 230 V | 230 V | 575 × 460 × 606 mm | 100 kg |
| 416B72TU2 | 16 kVA | 230 V | 230 V | 575 × 460 × 606 mm | 115 kg |
| 420B72TU2 | 20 kVA | 230 V | 230 V | 575 × 460 × 606 mm | 125 kg |
| 425B72TU2 | 25 kVA | 230 V | 230 V | 727 × 600 × 810 mm | 157 kg |
| 431B72TU2 | 31.5 kVA | 230 V | 230 V | 727 × 600 × 810 mm | 175 kg |
| 440B72TU2 | 40 kVA | 230 V | 230 V | 727 × 600 × 810 mm | 213 kg |
| 450B72TU2 | 50 kVA | 230 V | 230 V | 810 × 780 × 1105 mm | 290 kg |
Dimension reference
Dimensions A, B, C, d and e in the table correspond to those shown in this image.